US Navy Standard for NSSN
Military Power® Isolated UPS
PFC, Drawout Battery
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1452AB, 4000 VA UPS, with Intelligent PDU for US Navy appeared first on Rugged Systems.
]]>US Navy Standard for NSSN
Military Power® Isolated UPS
PFC, Drawout Battery
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The field proven Military Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-1452AB was specifically designed for US Navy NSSN Virginia Class Submarine rack systems requiring higher power requirements using minimal rack space. The ETI0001-1452 does not require a separate PDU since the PDU functions are already integrated into the UPS module. This saves rack space, cabling and expense while improving overall reliability.
This heavy-duty chassis occupies only 4U (7.0") of rack space while accommodating a front draw-out, hot-swap battery module. The chassis has rounded metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration in any axis. These units can be mounted horizontally or vertically.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115VAC, CONUS) and optional auto-ranging international input voltages (85-270 VAC,OCONUS). The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high-intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battle short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are unique allowing the use of either standard NEMA 5-15P plugs or MS threaded metal shell connectors. This reverse air flow version draws air through the front and exhausts out the rear vents into the rack. A removable and washable intake air filter and high capacity stainless steel ball-bearing fans provide added protection in both controlled and hostile environments. The ETI0001-1452 has the added benefit of having a field-replaceable battery via a front draw out battery module. The batteries are maintenance-free with immobilized electrolyte and are constructed of flame retardant materials
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more Products in this series:
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land-based systems combining advanced modular design features with highly reliable construction.
| AC OUTPUT | |
| Output voltage: | 120 VAC true sinewave standard, others optional |
| Output rating: UPS | 4000 VA standard in 4U chassis x 26″ deep 0.65 to 0.75 pf std, optional configurations to 24,000 VA |
| Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
| Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
| Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
| Harmonic distortion: | Less than 5.0% into 100% non-linear load |
| Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available 400 or 1000 Hz output available as an option |
| Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
| AC INPUT | |
| Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
| Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
| Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
| Input power factor: | Better than 99% typically |
| Input/output isolation: | 4000 VA, up to 120 dB common mode, <1.0 mA leakage |
| Input transient suppression: | Complies with IEEE 587 and UL 1449 |
| Input control/protection: | Guarded 2 pole input breaker w/ UPS fuses Optional cold start to turn on w/o AC present |
| Input power connection: | MS 3102A-22-2P, 3 pin, locking |
| INTERNAL BATTERY | |
| Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials, Oxygen Index 28+ |
| Internal battery life: | Rated for continuous service life of 5 years |
| Internal DC protection: | Panel mounted fuses standard, breaker optional |
| Internal battery replacement: | Drawout module from rear of unit |
| External battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
| DISTRIBUTION PANEL | |
| Output circuits: | Seven controlled outputs via solidstate relays |
| Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
| Output receptacles: | MS / NEMA 5-15R threaded locking, various options |
| MECHANICAL | |
| Dimensions ( H x D x W ): UPS | 7.0 (4U) x 26.0 x 19.0 in (178x660x483mm) |
| Rack Slide Mount Patterns: | Jonathan, General Devices patterns standard, others optional |
| Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
| Shipping weight: Total UPS w/o Battery Module Drawout Battery Module |
191 lb. ( 87 kg) with lift handles front and rear 104 lb. ( 47 kg) with lift handles front and rear 66 lb. ( 30 kg) with lift handles front |
| Audible noise: | Less than 47 dB @ 5.0 ft., ANSI “A” scale |
| Cooling type: | High capacity, positive pressure, forced air |
| Cooling air direction: | Front intake, exhaust to rear |
| Air intake filter: | Washable metal filter media, others optional |
| ENVIRONMENTAL | |
| Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
| Operating temperature: | 32° to 113° F ambient (0° to 45° C ), lower/ higher optional |
| Operating humidity: | 0 to 95% relative humidity (non-condensing) |
| Storage elevation: | Up to 40,000 ft (12,192 m) |
| Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
| STANDARDS | |
| United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
| Canada: | CSA C22.2 No. 107 UPS safety requirements |
| EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
The post ETI0001-1452AB, 4000 VA UPS, with Intelligent PDU for US Navy appeared first on Rugged Systems.
]]>The post ETI0001-1473 series, 2000 VA UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>Though it can use domestic VAC The optional auto-ranging 85-270 VACCONUS OCONUS)internal input transformer. he input circuit breaker and the galvanic isolation transformer provide a double pole isolated source for overseas locations where phase references and grounding are not consistent.
Special EMI/RFI filters and input power factor correction minimize both input current and harmonics.
The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front and rear panels also provide easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.
The internal intelligent thermal sensors provide two-stage monitoring of unit temperatures, with both local and remote capability of thermal shutdown. can be engaged via the front panel control, via a remote contact input or via a software command. When in , an audible alarm is sounded and an indicator is lit. The high-intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.
The rear panel provides locking connectors for the input and output power with various optional configurations available. This unit draws air through the front air filter and exhausts out the rear vent into the rack. This allows the unit to be used in either negative or neutral pressure racks. The fan is a special extra quiet version to keep the unit’s overall audible level below 44 dB.
The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability PDU Remote Control connector provide an interface to optional remote display/control panels. The RJ45 LAN port provides an SNMP/HTTP interface for various UPS parameters.
The batteries are maintenance-free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. See the Power Distribution Units section for a listing of stand-alone PDUs. See the N3 Series for a version of UPS without the integrated PDU and remote control.
In addition to the original ETI0001-1473 there is also available in this series:
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1473 series, 2000 VA UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>US Navy IT-21, SNAP III, JMOC, ADNS,MAST,SPAWAR Standard Product
Military Power®Configuration with Ethernet 10BaseT Communications
Isolated UPS, 2000 VA Rugged Rack Mount UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1467, 4000 VA UPS, with Intelligent PDU for Navy: IT-21, SNAP III, JMOC, ADNS appeared first on Rugged Systems.
]]>The rear panel provides locking connectors for the input and output power with various optional configurations available. The washable air filters and high capacity ball bearing fan provide added protection in both controlled and hostile environments. The external battery connector allows the safe and easy addition of extra battery modules without having to shut the unit down. A frequency selection switch is available for those sites requiring 50-hertz output instead of the standard60-hertz. The status D shell connector provides signals to interface with optional computer software providing loss of AC and low battery status. The RJ45 LAN port provides an SNMP/HTTP interface for various UPS parameters.
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1467, 4000 VA UPS, with Intelligent PDU for Navy: IT-21, SNAP III, JMOC, ADNS appeared first on Rugged Systems.
]]>US Navy Military Power® MilSpec N5 Configuration
2000 VA Rugged Rack MountIsolated UPS w/ Integrated
6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
With Drip Proof Front Panel, Shallow Depth, Removable Battery
The post ETI0001-1458, 2000 VA UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. All controls and protective devices are brought to the front panel with critical switches or breakers guarded. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battle-short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console with only a logic level cable connection. Both the input circuit breaker and isolation transformer provide double pole isolation for shipboard systems.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are unique allowing the use of either standard NEMA 5-15P plugs or MS threaded metal shell connectors. The washable air filters and high capacity ball bearing fan provide added protection in both controlled and hostile environments. The external battery connector allows the safe and easy addition of extra battery modules without having to shut the unit down. The status D shell connectors provide signal interfaces with optional computer software and the remote display/control panels.
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1458, 2000 VA UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>Military Power® Isolated Mil Spec UPS, Rugged Rack Mount UPS
w/ PFC and Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1457 UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optional auto-ranging international input voltages (85-270 VAC,OCONUS). The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battle-short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are standard NEMA 5-15R with unique cable restraints. This reverse air flow version draws air through the front and exhausts out the rear vents into the rack. A removable and washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments.
The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials.
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more information see the Power Distribution Units section for a listing of stand alone PDUs
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1457 UPS, with Intelligent PDU appeared first on Rugged Systems.
]]>Elbit / Ingalls Shipbuilding Standard for Venezuelan Navy
Military Power® Isolated Mil Spec UPS, 4000 VA Rugged Rack Mount UPS
w/ PFC and Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1456, 4000 VA UPS, with Intelligent PDU for Venezuelan Navy appeared first on Rugged Systems.
]]>Both chassis have rounded metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration in any axis. These units can be mounted horizontally or vertically.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optional auto-ranging international input voltages (85-270 VAC,OCONUS). The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battle-short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are standard NEMA 5-15R with unique cable restraints. This reverse air flow version draws air through the front and exhausts out the rear vents into the rack. A removable and washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments.
The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials.
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more information see the Power Distribution Units section for a listing of stand alone PDUs
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1456, 4000 VA UPS, with Intelligent PDU for Venezuelan Navy appeared first on Rugged Systems.
]]>P/N: ETI0001-1455, Raytheon / US Navy Standard for NSSN
Ultra Compact Isolated Mil Spec UPS
4000 VA Rugged Rack Mount UPS w/ PFC, Drawout Battery and
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1455, 4000 VA UPS, with Intelligent PDU for NSSN appeared first on Rugged Systems.
]]>This heavy-duty chassis occupies only 4U (7.0″) of rack space while accommodating a front drawout, hot-swap battery module. The chassis has rounded metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration in any axis. These units can be mounted horizontally or vertically.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optional autoranging international input voltages (85-270 VAC, OCONUS). Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battleshort override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are Hubbell 7487 twist lock which use a very shallow depth mating plug. This reverse air flow version draws air through the front and exhausts out the rear vents into the rack. A removable and washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The “ETI0001-1455” has the added benefit of having a field replaceable battery via a front drawout battery module. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials.
The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials.
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more information see the Power Distribution Units section for a listing of stand alone PDUs
Also available is the ETI0001-1455AB. Inquire for details on this variant.
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1455, 4000 VA UPS, with Intelligent PDU for NSSN appeared first on Rugged Systems.
]]>Military Power®
NSWC Standard Configuration for MK 119 MOD 0 Gun Computing System
Isolated Mil Spec UPS, 4000 VA Rugged Rack Mount UPSw/ PFC
Integrated 6 Circuit, 2 Pole, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1453, 4000 VA UPS, with Intelligent PDU for MK 119 appeared first on Rugged Systems.
]]>The 3Uelectronics module can be mounted in the upper section of the rack near eyelevel or lower in the rack near the battery module. The heavier 2U battery module is usually mounted in the bottom of the rack for lowering the center of gravity of the rack. A heavy duty shielded cable is provided to connect the two modules. Both chassis have rounded metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration in any axis. These units can be mounted horizontally or vertically.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. To provide added flexibility and reliability, the “ETI0001-1453” accepts two independent AC power sources. The UPS can operate from either power source automatically and does not use its battery unless both sources have failed.
The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interface sfor additional control and safety, plus Battle-short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are MS threaded metal shell connectors. This unit draws air through the rear and exhausts out the side vents into the rack. This allows the unit to be used in either positive, negative or neutral pressure racks. A removable and washable intake air filter and high capacity stainless steel ball-bearing fans provide added protection in both controlled and hostile environments.
The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials.
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more information see the Power Distribution Units section for a listing of stand alone PDUs
The other unit in this series is the ETI0001-1453AB.
Please inquire in the form below for more details on this variant.
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1453, 4000 VA UPS, with Intelligent PDU for MK 119 appeared first on Rugged Systems.
]]>The post ETI0001-1451 series, 4000 VA UPS, with Intelligent PDU for Navy TAMPS & Q70 appeared first on Rugged Systems.
]]>For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more information see the Power Distribution Units section for a listing of stand alone PDUs Inquire for information on the versions of this unit:
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
The post ETI0001-1451 series, 4000 VA UPS, with Intelligent PDU for Navy TAMPS & Q70 appeared first on Rugged Systems.
]]>US Navy Standard for NSSN
Military Power® Isolated UPS
PFC, Drawout Battery
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The post ETI0001-1452 Series, 4000 VA UPS, with Intelligent PDU for US Navy NSSN appeared first on Rugged Systems.
]]>US Navy Standard for NSSN
Military Power® Isolated UPS
PFC, Drawout Battery
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
The field proven Military Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The
ETI0001-1452 was specifically designed for US Navy NSSN Virginia Class Submarine rack systems requiring higher power requirements using minimal rack space. The ETI0001-1452 does not require a separate PDU since the PDU functions are already integrated into the UPS module. This saves rack space, cabling and expense while improving overall reliability.
This heavy-duty chassis occupies only 4U (7.0") of rack space while accommodating a front draw-out, hot-swap battery module. The chassis has rounded metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration in any axis. These units can be mounted horizontally or vertically.
The internal shielded input transformer provides galvanic isolation with provisions for domestic (115VAC, CONUS) and optional auto-ranging international input voltages (85-270 VAC,OCONUS). The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to 60 hertz power. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. The internal intelligent PDU allows control of the individual output circuits incorporating thermal and interlock interfaces for additional control and safety, plus Battle short override. The display and control panel can be mounted remotely in the rack at eye level, or on the keyboard console, or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power with various optional configurations available. The output connectors are unique allowing the use of either standard NEMA 5-15P plugs or MS threaded metal shell connectors. This reverse air flow version draws air through the front and exhausts out the rear vents into the rack. A removable and washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The ETI0001-1452 has the added benefit of having afield replaceable battery via a front draw out battery module. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials
For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.
For more Products in this series:
Overall, the Outdoor Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.
| AC OUTPUT | |
| Output voltage: | 120 VAC true sinewave standard, others optional |
| Output rating: UPS | 4000 VA standard in 4U chassis x 26″ deep 0.65 to 0.75 pf std, optional configurations to 24,000 VA |
| Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
| Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
| Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
| Harmonic distortion: | Less than 5.0% into 100% non-linear load |
| Output frequency: UPS | 60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available 400 or 1000 Hz output available as an option |
| Operational status | Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
| AC INPUT | |
| Input voltage selection: | Nominal 115 VAC, optional autoranging input of 85-270 VAC |
| Input voltage tolerance: UPS | 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load |
| Input frequency: | From 46 Hz to 70 Hz standard, optional to 440 Hz |
| Input power factor: | Better than 99% typically |
| Input/output isolation: | 4000 VA, up to 120 dB common mode, <1.0 mA leakage |
| Input transient suppression: | Complies with IEEE 587 and UL 1449 |
| Input control/protection: | Guarded 2 pole input breaker w/ UPS fuses Optional cold start to turn on w/o AC present |
| Input power connection: | MS 3102A-22-2P, 3 pin, locking |
| INTERNAL BATTERY | |
| Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials, Oxygen Index 28+ |
| Internal battery life: | Rated for continuous service life of 5 years |
| Internal DC protection: | Panel mounted fuses standard, breaker optional |
| Internal battery replacement: | Drawout module from rear of unit |
| External battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
| DISTRIBUTION PANEL | |
| Output circuits: | Seven controlled outputs via solidstate relays |
| Output control: | Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
| Output receptacles: | MS / NEMA 5-15R threaded locking, various options |
| MECHANICAL | |
| Dimensions ( H x D x W ): UPS | 7.0 (4U) x 26.0 x 19.0 in (178x660x483mm) |
| Rack Slide Mount Patterns: | Jonathan, General Devices patterns standard, others optional |
| Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
| Shipping weight: Total UPS w/o Battery Module Drawout Battery Module |
191 lb. ( 87 kg) with lift handles front and rear 104 lb. ( 47 kg) with lift handles front and rear 66 lb. ( 30 kg) with lift handles front |
| Audible noise: | Less than 47 dB @ 5.0 ft., ANSI “A” scale |
| Cooling type: | High capacity, positive pressure, forced air |
| Cooling air direction: | Front intake, exhaust to rear |
| Air intake filter: | Washable metal filter media, others optional |
| ENVIRONMENTAL | |
| Storage temperature: | -40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
| Operating temperature: | 32° to 113° F ambient (0° to 45° C ), lower/ higher optional |
| Operating humidity: | 0 to 95% relative humidity (non-condensing) |
| Storage elevation: | Up to 40,000 ft (12,192 m) |
| Operating elevation: | Up to 15,000 ft (4,572 m), higher optional |
| STANDARDS | |
| United States: | Meets UL-1778 standard for UPS equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
| Canada: | CSA C22.2 No. 107 UPS safety requirements |
| EMI Protection: | EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 |
The post ETI0001-1452 Series, 4000 VA UPS, with Intelligent PDU for US Navy NSSN appeared first on Rugged Systems.
]]>