The field-proven WorldPower™ UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-2229 series is specifically designed for lightweight global power by the US Navy as the power source for critical systems because of the stringent performance and reliability requirements.

The heavy-duty chassis, occupying only 5.25”(3U) of rack space while delivering up to 2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles front and rear, aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. These units can be mounted horizontally or vertically. Optional heavy-duty rack slides provide easy installation and removal of the unit with full extension.

The internal shielded input transformer provides galvanic isolation with provisions for both domestic (115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. The auto-ranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. Optionally, 46-440 hertz input and 50 or 400 hertz outputs are available.

The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.

The internal intelligent thermal sensors provide two-stage monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown. Battle-short can be engaged via the front panel control, via a remote contact input or via a software command. When in Battle-short, an audible alarm is sounded and an indicator is lit. The high-intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

All controls and protective devices are brought to the front and rear panels with critical switches or circuit breakers having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Clips on the front panel hold spare fuses for ready access. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for shipboard systems or overseas locations where phase references and grounding are not consistent. The manual bypass feature included is operated from the front panel. Even in the bypass mode, the ETI0001-2229 still provides galvanic isolation, transient surge protection and EMI/RFI filtering.

The ETI0001-2229 has the added benefit of having a field-replaceable battery via a front draw-out battery module. The battery is a true hot-swappable module and does not require going to bypass like competing units. Even with this battery module removed, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well-regulated, sinusoidal power to the load. The batteries are maintenance-free with immobilized electrolyte and are constructed of flame retardant materials for added safety.

For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Other Units in this series include:

  • ETI0001-2229A1
  • ETI0001-2229AG: NSN: 6130-01-569-3589- US Navy AN/TPX-42A(V)14 FC3 Configuration for CV, CVN, LHA & LHD
  • ETI0001-2229AJ: NSN: 6130-01-601-0706 
  • ETI0001-2229AM: NSN: 6130-01-572-5104 with Remote Control
  • ETI0001-2229AN
  • ETI0001-2229E: (Replaces NSN: 6130-01-560-7789) with 2000 VA / 1400 Watts, 90-264 VAC and 120*/100/110 VAC

Please use the contact form below to inquire about these variants.

Overall, the World Power line is uniquely qualified for critical shipboard, vehicle, airborne or land-based systems combining advanced modular design features with highly reliable construction.

ETI0001-2229 series, 2000 VA, Global Rackmount UPS for SSDS

Rugged MilSpec®2000 VA Rackmount Global UPS

NSN #: 6130-01-544-8782

  • US Navy / Raytheon SSDS (Ship Self Defense System) Configuration
  • Dept. of the Navy P/N: 40NKPT0009
  • WorldPower™ Rugged MilSpec® Rack Mount 2.0 kVA UPS
  • Autoranging
  • Global Isolated
  • Input Accepts 85-270 VAC, 46-70 Hz
  • Input PFC
  • Battleshort
  • Manual Bypass
  • Elapsed Time Meter
  • Front Access Hot Swappable Battery Module
  • Backward Compatible for Refitting Existing SSDS Systems

The field-proven WorldPower™ UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-2229 series is specifically designed for lightweight global power by the US Navy as the power source for critical systems because of the stringent performance and reliability requirements.

The heavy-duty chassis, occupying only 5.25”(3U) of rack space while delivering up to 2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles front and rear, aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. These units can be mounted horizontally or vertically. Optional heavy-duty rack slides provide easy installation and removal of the unit with full extension.

The internal shielded input transformer provides galvanic isolation with provisions for both domestic (115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. The auto-ranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. Optionally, 46-440 hertz input and 50 or 400 hertz outputs are available.

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.

The internal intelligent thermal sensors provide two-stage monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown. Battle-short can be engaged via the front panel control, via a remote contact input or via a software command. When in Battle-short, an audible alarm is sounded and an indicator is lit. The high-intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

All controls and protective devices are brought to the front and rear panels with critical switches or circuit breakers having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Clips on the front panel hold spare fuses for ready access. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for shipboard systems or overseas locations where phase references and grounding are not consistent. The manual bypass feature included is operated from the front panel. Even in the bypass mode, the ETI0001-2229 still provides galvanic isolation, transient surge protection and EMI/RFI filtering.

The ETI0001-2229 has the added benefit of having a field-replaceable battery via a front draw-out battery module. The battery is a true hot-swappable module and does not require going to bypass like competing units. Even with this battery module removed, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well-regulated, sinusoidal power to the load. The batteries are maintenance-free with immobilized electrolyte and are constructed of flame retardant materials for added safety.

For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Other Units in this series include:

  • ETI0001-2229A1
  • ETI0001-2229AG: NSN: 6130-01-569-3589- US Navy AN/TPX-42A(V)14 FC3 Configuration for CV, CVN, LHA & LHD
  • ETI0001-2229AJ: NSN: 6130-01-601-0706 
  • ETI0001-2229AM: NSN: 6130-01-572-5104 with Remote Control
  • ETI0001-2229AN
  • ETI0001-2229E: (Replaces NSN: 6130-01-560-7789) with 2000 VA / 1400 Watts, 90-264 VAC and 120*/100/110 VAC

Please use the contact form below to inquire about these variants.

Overall, the World Power line is uniquely qualified for critical shipboard, vehicle, airborne or land-based systems combining advanced modular design features with highly reliable construction.

Technical Specifications

AC OUTPUT
Output voltage: 120 VAC true sinewave output standard
Output rating: UPS 2000 VA, 1500 watts standard
For 1000 VA, 750 watts, see ETI0001-2227
For 1000 VA, 750 watts, see ETI0001-2227AC (w/DC Input)
https://ruggedups.com/product/eti0001-2228-1500-va-global-rackmount-ups-for-ssds/
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 2.5% synchronized to utility
60 Hz ± 1.0% w/ utility not available
Operational status AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload, Warm temperature, Hot temperature, Manual bypass and Battleshort LEDs, Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
Asynchronous serial COM port
AC INPUT
Input voltage selection: Autoranging from nominal 115 VAC to 230 VAC
Input voltage tolerance: UPS +15% -25%, or 85-135 and 170-270
@ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 2000 VA, up to 120 dB common mode, <1.0 ma leakage
Input transient suppression: Complies with IEEE 587, UL 1449 and Mil Std 1399
Input control/protection: Guarded 2 pole 100 G shock rated circuit breaker (CB1)
plus UPS input fuse (F2), spare fuse on front
Manual bypass switch to force bypass mode
Optional cold start switch available to turn on w/o AC present
Input power connections: One MS 3102A-22-2P, 3 pin, locking
INTERNAL BATTERY
Internal battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal battery life: Rated for continuous service life of 5 years
Internal battery protection: Front panel mounted fuse (F1), spare fuse on front
Internal battery time: 6+ minutes @ 1500 watts,10+ minutes @ 1000 watt load
Internal battery recharge: Recharged to nominal in <8 hours
Internal battery replacement: Hot swap drawout/plug-in module from front of unit
<3 minutes to change battery modules
Battery expansion: Up to 24 hours w/ optional Battery Expansion Modules
DISTRIBUTION PANEL
Output circuits: Six AC outputs standard, several optional configurations
Output control: Only via CB1; optional remote control panel w/switches available
Output receptacles: AC output NEMA 5-15R with locking cable bales standard, various options
MECHANICAL
Dimensions (H x D x W): UPS 5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns standard, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight:
UPS and Battery
UPS only
Battery Module only
105 lb. (48 kg) with lift handles front and rear
65 lb. (30 kg) with lift handles front and rear
40 lb. (18 kg) with lift handle in front
Audible noise: Less than 47 dB @ 5.0 ft., ANSI “A” scale
Cooling type: High capacity, negative pressure, forced air
Cooling air direction: Front intake, exhaust to rear, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C)
Operating temperature: 32° to 126° F ambient ( 0° to 52° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m), higher optional
Operating elevation: Up to 10,000 ft (3,048 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A & MIL-S-901
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461

Product Support Services

Warranty Coverage

  1. First Year Standard Warranty- The Energy Technologies’ Standard Warranty covers labor and material (excluding batteries) for the first year after shipment; however, this warranty excludes travel and living expenses. Refer to the Warranty section of this manual.
  2. Extended Warranty (Optional)- For those customers who desire to purchase service over and above the Standard Warranty, ETI will provide a quote for a service plan to meet your requirements. Typical plans include the following:
  3. Extended Warranty OptionThis plan provides for replacement parts as an extension to the Standard Warranty one-year period.
  4. Limited Full Service Plan OptionThe Limited Full Service Plan extends the Standard Warranty beyond the initial one-year period, and includes travel and living expenses for the warranty period. This plan can be offered with or without preventive maintenance.

 

Return Material Authorization

If the product requires service for any reason, the customer should contact the Customer Service Department. If the product must be returned to ETI for repair or replacement, the customer must obtain a Return Materials Authorization (RMA) number. The product must be packed in the original shipping container or other equally suitable container. The product must be shipped prepaid with the RMA number on the packing slip. Unauthorized returns of units will be subject to an inspection and handling charge plus any repair and all transportation charges.

Note

If you have to return the unit for repair, it is imperative that it be packaged properly! Due to the weight of the unit and the potential for mishandling, the unit carton must be strapped to a skid before shipping. This forces the freight company to use a tow motor to move the unit. When a skid is not used, there are stages in handling where the carton will be manhandled and inevitably gets dropped on its ends. Foam packs and other packing fillers alone are not adequate to avoid mechanical damage. Energy Technologies, Inc. will not be liable and a breach of warranty will occur if:
1) a skid is not used
2) proper handling is not maintained.

 

Standard Warranty Policy

Energy Technologies, Incorporated (ETI) warrants against faulty materials or workmanship for equipment sold new and delivered pursuant to the terms of any agreement between ETI and customer for one (1) year from the original date of shipment of the equipment. The warranty is limited to repair or replacement during the warranty period at the sole discretion of ETI. It is the responsibility of the customer to notify and return the defective product to ETI, with all costs for shipment of the product to and from ETI paid by the customer. The defective product must be returned intact and shall appear to ETI upon inspection that the failure of the product was caused by defective material or workmanship. Such repair or replacement shall be made free of charge if the defect is determined to be caused from faulty material and/or workmanship, the unit is within the warranty period, and ETI was notified within the warranty period.

This warranty, however,
(a) extends only to, and is intended for the benefit only of, customer (original purchaser), and does not obligate, and shall not be construed to obligate, ETI to any person or organization other than customer.
(b) is effective only when customer returns such defective part or parts to ETI’s factory, transportation prepaid, immediately upon customer’s discovery of the defect in question.
(c) is not effective when the part or product in question is, or has been, operated beyond rated capacity, used or applied improperly, or used with parts which are not made or recommended by ETI.
(d) does not render ETI liable for any claims or claims for damages which may result, directly or indirectly, from any defect in any part or parts manufactured by ETI; except to replace the part or parts in question.

In lieu of returning defective part or parts to ETI’s factory as specified in subparagraph (b) of the foregoing standard warranty, the customer may request ETI to make necessary repairs on site. If ETI agrees that such on-site repairs are practical, ETI shall supply parts and labor for this purpose free of charge; however, the customer shall pay ETI’s traveling expenses to and from said site and living expenses of such personnel while traveling and while on site. If the required repairs are found to be caused by the mishandling, misuse or misapplication of equipment furnished by ETI and/or the required repairs are covered by the ETI Operations and Maintenance Manual, then ETI shall supply labor at the per diem rate normally charged for field service. Parts to be in accordance with ETI’s spare parts prices.

The warranty shall be void if:
(a) the equipment is damaged by the customer, is improperly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications.
(b) the equipment is repaired or modified by anyone other than ETI or ETI approved personnel.
(c) has been used in a manner contrary to the products operating manual or other written instructions.

ETI reserves the right to make changes, additions, and/or improvements in its products without incurring any obligation to install them on its products previously manufactured and/or sold. No provision of this warranty shall cover the installed batteries. However, the battery manufacturer’s warranties shall be passed through to the customer whenever applicable. ETI will not be liable for any associated costs incurred by the user or installing contractor as a direct or indirect result of failure or in the replacement of defective in-warranty material. The customer MUST obtain a Return Material Authorization from ETI’s Customer Service Department before returning a product for warranty service. The return authorization number MUST be placed on the outside of the shipping box and the equipment must be packaged securely to avoid damage during shipping. Unauthorized returns for in-warranty repairs may be rejected or subject to an inspection and handling charge of $75 plus any repair and all transportation charges.

The warranty is expressly in lieu of all other warranties, expressed or implied, including, and without limitation, any implied warranty or merchantability or fitness for a particular purpose, and/or any other obligation or liability on the part of Energy Technologies Inc. The sole exclusive remedy for breach of any warranty, expressed or implied, concerning ETI’s products and the only obligation of ETI hereunder, shall be the repair or replacement of defective equipment, components, or parts, or, at ETI’s option, the refund of the purchase price or substitution with a new replacement product. ETI shall in no way be responsible for any consequential damages, of any kind, or nature whatsoever, resulting from the breach of any warranty.