The field proven Military Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-2227 series is specifically designed for lightweight global power by the US Navy as the power source for critical systems because of the stringent performance and reliability requirements.

The heavy-duty chassis, occupying only 5.25”(3U) of rack space while delivering up to 1000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles front and rear, aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.  These units can be mounted horizontally or vertically. Optional heavy-duty rack slides provide easy installation and removal of the unit with full extension.

The internal shielded input transformer provides galvanic isolation with provisions for both domestic(115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. The auto-ranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. Optionally, 46-440 hertz input as well either 50 or 400 hertz outputs are available.

The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.

The internal intelligent thermal sensors provide two stage monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown. Battle-short can be engaged via the front panel control, via a remote contact input or via a software command. When in Battle short, an audible alarm is sounded and an indicator is lit. The high intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

All controls and protective devices are brought to the front and rear panels with critical switches or circuit breakers having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Clips on the front panel hold spare fuses for ready access. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. The manual bypass feature included is operated from the front panel. Even in the bypass mode, the ETI0001-2227 still provides galvanic isolation, transient surge protection and EMI/RFI filtering.

The ETI0001-2227 has the added benefit of having a field replaceable battery via front draw-out battery module. The battery is a true hot-swappable module and does not require going to bypass like competing units. Even with this battery module removed, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well regulated, sinusoidal power to the load. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials for added safety. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Other Units in this series include:

  • ETI0001-2227AA: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AB: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AC: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AD: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AE: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AF: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AG: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227E: Replaces NSN: 6130-01-388-6638 and 6130-01-553-3855 with
    Global AC Input, Field Replaceable Battery Drawer, Battleshort, Manual Bypass

Please use the contact form below to inquire about these variants.

Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

ETI0001-2227, 1000 VA, Global Rackmount UPS

NSN: 6130-01-526-9079
Rugged Mil Spec® 1000 VA Rackmount Global UPS

  • US Navy / US Marine Corps Standard Configuration
  • Military Power® Rugged Mil Spec Rack Mount 1.0 kVA UPS
  • Autoranging Global Isolated Input
  • Accepts 85-270 VAC, 46-70 Hz
  • Input PFC
  • Battleshort
  • Manual Bypass
  • Elapsed Time
  • Plus Front Access Hot Swappable Battery Module

The field proven Military Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-2227 series is specifically designed for lightweight global power by the US Navy as the power source for critical systems because of the stringent performance and reliability requirements.

The heavy-duty chassis, occupying only 5.25”(3U) of rack space while delivering up to 1000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles front and rear, aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.  These units can be mounted horizontally or vertically. Optional heavy-duty rack slides provide easy installation and removal of the unit with full extension.

The internal shielded input transformer provides galvanic isolation with provisions for both domestic(115 VAC, CONUS) and international (230 VAC, OCONUS) input voltages. The auto-ranging input voltage selection allows inputting either 115 VAC or 230 VAC without having to open the UPS enclosure. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. Optionally, 46-440 hertz input as well either 50 or 400 hertz outputs are available.

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The Elapsed Time Indicator records the number of operational hours for records and scheduling preventative maintenance of attached equipment. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to less than 15 minutes.

The internal intelligent thermal sensors provide two stage monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown. Battle-short can be engaged via the front panel control, via a remote contact input or via a software command. When in Battle short, an audible alarm is sounded and an indicator is lit. The high intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

All controls and protective devices are brought to the front and rear panels with critical switches or circuit breakers having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Clips on the front panel hold spare fuses for ready access. The input circuit breaker and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. The manual bypass feature included is operated from the front panel. Even in the bypass mode, the ETI0001-2227 still provides galvanic isolation, transient surge protection and EMI/RFI filtering.

The ETI0001-2227 has the added benefit of having a field replaceable battery via front draw-out battery module. The battery is a true hot-swappable module and does not require going to bypass like competing units. Even with this battery module removed, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well regulated, sinusoidal power to the load. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials for added safety. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Other Units in this series include:

  • ETI0001-2227AA: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AB: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AC: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AD: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AE: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AF: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227AG: US Navy Shipboard Product with Front Access Hot Swap Battery
  • ETI0001-2227E: Replaces NSN: 6130-01-388-6638 and 6130-01-553-3855 with
    Global AC Input, Field Replaceable Battery Drawer, Battleshort, Manual Bypass

Please use the contact form below to inquire about these variants.

Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

Additional information

Weight 93 lbs
Dimensions 23 × 19 × 10.5 in

Technical Specifications

NSN: 6130-01-526-9079

AC OUTPUT
Output voltage: 120 VAC true sinewave output standard
Output rating: UPS 1000 VA, 750 watts standard
For 1500 VA, 1125 watts, see ETI0001-2228   
For 2000 VA, 1500 watts, see
ETI0001-2229
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 2.5% synchronized to utility
60 Hz ± 1.0% w/ utility not available
50, 400 or 1000 Hz output available as an option
Operational status AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload, Warm temperature, Hot temperature, Manual bypass and Battle-short LEDs, Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
Asynchronous serial COM port
AC INPUT
Input voltage selection: Auto-ranging from nominal 115 VAC to 230 VAC
Input voltage tolerance: UPS +15% -25%, or 85-135 and 170-270
@ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 2000 VA, up to 120 dB common mode, <1.0 mA leakage
Input transient suppression: Complies with IEEE 587, UL 1449 and Mil Std 1399
Input control/protection: Guarded 2 pole 100 G shock rated circuit breaker (CB1)
plus UPS input fuse (F2), spare fuse on front
Manual bypass switch to force bypass mode
Optional cold start switch available to turn on w/o AC present
Input power connections: One MS 3102A-22-2P, 3 pin, locking
INTERNAL BATTERY
Internal Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal Rated for continuous service life of 5 years
Internal Front panel mounted fuse (F1), spare fuse on front
Internal battery time: 10+ minutes @ 700 watts
Internal battery recharge: Recharged to nominal in <8 hours
Internal battery replacement: Hot swap draw-out/plug-in module from front of unit
<3 minutes to change battery modules
Battery expansion: Up to 24 hours w/ optional Battery Expansion Modules
DISTRIBUTION PANEL
Output circuits: Six (6) AC outputs standard, several optional configurations
Output control: Only via CB1; optional remote control panel w/switches available
Output receptacles: AC output NEMA 5-15R with locking cable bales standard, various options
MECHANICAL
Dimensions (H x D x W): UPS 5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns standard, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: UPS and Battery
UPS only
Battery Module only
93 lb. (43 kg) with lift handles front and rear
65 lb. (30 kg) with lift handles front and rear
28 lb. (13 kg) with lift handle in front
Audible noise: Less than 47 dB @ 5.0 ft., ANSI “A” scale
Cooling type: High capacity, negative pressure, forced air
Cooling air direction: Front intake, exhaust to rear, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461