The field-proven PowerStation UPS line is ideally suited for military, industrial and telecommunications applications requiring rugged rack or table mount and/or portable construction, high reliability, compact size and lightweight design. The heavy-duty chassis occupies minimal space while delivering up to 1000 VA of clean, uninterruptible power. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.

An internal transformer bay accommodates the input isolation transformer with provisions for both domestic and optional international voltages for ratings up to 1000 VA. The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high-intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. Various optional power distribution controls are available which mount internally or remotely.

Locking connectors for the input and output power are available as options. Multiple input and output power panel options are also available. A washable intake air filter and high capacity ball bearing fan provide added protection in both controlled and hostile environments. The exhaust air is diverted outside vents. An external battery connector allows the safe and easy addition of extra battery modules without having to shut the unit down.

A frequency selection switch is available for those sites requiring 50-hertz output instead of the standard 60 hertz. The status D shell connector provides signals to interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability. Overall, the PowerStation line is uniquely qualified for critical industrial, shipboard, vehicle, airborne or land-based systems combining advanced modular design features with highly reliable construction.

Also available:

ETI0005-1016 120/240 VAC, 50/60 Hz 1 kVA 120 VAC, 50/60 Hz 80 min MANUAL BYPASS SWITCH/Mil-Spec
• ETI0005-1016AD 120VAC, 50/60Hz 2 kVA 120VAC, 50/60Hz 120 min MANUAL BYPASS SWITCH
• ETI0005-1016AG 120/240 VAC, 50/60 Hz 1 kVA 120 VAC, 50/60 Hz No Batt. Autoranging

ETI0005-1016AB, 1000 VA Rugged NEMA UPS

Part #: ETI0001-1016AB
PowerStation™Isolated UPS
1000 VA Rugged NEMA, Modular Power System

The field-proven PowerStation UPS line is ideally suited for military, industrial and telecommunications applications requiring rugged rack or table mount and/or portable construction, high reliability, compact size and lightweight design. The heavy-duty chassis occupies minimal space while delivering up to 1000 VA of clean, uninterruptible power. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.

An internal transformer bay accommodates the input isolation transformer with provisions for both domestic and optional international voltages for ratings up to 1000 VA. The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high-intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. Various optional power distribution controls are available which mount internally or remotely.

Locking connectors for the input and output power are available as options. Multiple input and output power panel options are also available. A washable intake air filter and high capacity ball bearing fan provide added protection in both controlled and hostile environments. The exhaust air is diverted outside vents. An external battery connector allows the safe and easy addition of extra battery modules without having to shut the unit down.

A frequency selection switch is available for those sites requiring 50-hertz output instead of the standard 60 hertz. The status D shell connector provides signals to interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability. Overall, the PowerStation line is uniquely qualified for critical industrial, shipboard, vehicle, airborne or land-based systems combining advanced modular design features with highly reliable construction.

Also available:

ETI0005-1016 120/240 VAC, 50/60 Hz 1 kVA 120 VAC, 50/60 Hz 80 min MANUAL BYPASS SWITCH/Mil-Spec
• ETI0005-1016AD 120VAC, 50/60Hz 2 kVA 120VAC, 50/60Hz 120 min MANUAL BYPASS SWITCH
• ETI0005-1016AG 120/240 VAC, 50/60 Hz 1 kVA 120 VAC, 50/60 Hz No Batt. Autoranging

Additional information

Weight 105 lbs
Dimensions 23.5 × 19 × 5.25 in

Technical Specifications

ETI0001-1016AB

 

ETI0005-1016
AC OUTPUT
Output voltage: 120 VAC true sinewave std, optional outputs
Output rating: UPS 1000VA
Non-linear load capacity: Up to 100% non-linear load capability
Output voltage regulation: UPS ± 3.0% static, ± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 or 50 Hz ± 2.5% when synchronized to input frequency

± 1.0% when input frequency is out of range or not present

Operational status: Status, load and battery (15) LED’s, w/contacts

RS-232, adjustable level, +90 dB audible alarm w/on/off

AC INPUT
Input voltage selection: 120/240 VAC standard 50/60 Hz
Input voltage tolerance: UPS +15% -25% of nominal input rating
Input/output isolation: Up to 120 dB common mode attenuation
Input transient suppression: Meets ANSI C62.41 1980, IEEE 587 standards
Input control/protection: Guarded 2 pole switch (S1) w/panel mounted fuse (F2)
Input power connection: Terminal Block
BATTERY
Type: Maintenance free immobilized electrolyte, 48VDC

Flame retardant materials (Oxygen Index 28+)

Battery life: Rated for continuous service life of 5 years
DC protection: Guarded fuse (F1)
Battery expansion: Up to 24 hours w/ Battery Extension Modules
DISTRIBUTION PANEL
Output circuits: Terminal Block
Output control: Optional panel switches or breakers or PDU
Output receptacles: Terminal Block
MECHANICAL
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Audible noise: Less than 47 dB @ 5.0 ft., ANSI “A” scale
Cooling type: High capacity, positive pressure, forced air
Air Intake Filter Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature:  -4° to 122° F ambient  (-20° to 50° C)
Operating temperature: 32° to 113° F ambient  (0° to 45° C)
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m), higher optionally
Operating elevation: Up to 10,000 ft (3,048 m), higher optionally
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,

MIL STDs 810, 454 & 1399 Shock/Vib/Electrical

Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC, Class A, opt MIL STDs 461 & 462
OPTIONS AVAILABLE
Rack mount power ratings to 6kVA, Dual Source Input, Battery Expansion Units, Power Distribution Units, Software Interfaces and Transport Cases

Tell Us About Your Needs

*(denotes required field)
prime contractors

Contact ETI by mail at:
Energy Technologies, Inc.
219 Park Avenue East
Mansfield, OH 44902-1845
USA

Contact ETI by phone or fax:
Voice: 419-522-4444
FAX: 419-522-4466

// code for product search below