The field-proven Tactical Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size, and lightweight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed, or fixed locations with controlled or uncontrolled environments. The ETI0001-2205 is being used as a power source in global defense applications because of the stringent performance and reliability requirements. 

The heavy-duty UPS and Battery chases have rounded metal corners and rugged handles front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.  The internal intelligent thermal sensors provide monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown for emergency scenarios. Battle-short can be engaged via a remote contact input or via a software command. When in Battle-short, an audible alarm is sounded and an indicator is lit. The high-intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

The internal shielded input transformer provides galvanic isolation with provisions for nominal 100, 115, 120, 208, 220, 230, and 240 VAC input voltages, 50 or 60 Hz. Special EMI/RFI filters, input power factor correction, and inrush current limiting minimize both input current and harmonics.

The built-in Elapsed Time Indicator logs the hours of operation of the UPS as well as that of the equipment powered by the UPS. This can be used to plan preventative maintenance of the entire system. The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high-intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the onboard spare fuses, MTTR is reduced to less than 15 minutes.

Further, all front panel devices are recessed to prevent damage or accidental operation. The input circuit breaker and the galvanic isolation transformers all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. The Maintenance Bypass Switch can be used to remove the UPS electronics module from service while still providing power to the connected loads.

The rear panel provides locking connectors for the input and output power. Removable, washable air filters combined with high capacity stainless steel ball-bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the rear vents, with alternate airflow directions optional.

The ETI0001-2205 has the added benefit of having a field-replaceable battery via a front draw-out battery module. The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance-free with immobilized electrolytes and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

Also available in this product series:

  • ETI0001-2205E2
  • ETI0001-2205A3
  • ETI0001-2205E1 The standard height version (6U total versus 5U) of this unit that is totally backward compatible.
  • ETI0001-2205AA
  • ETI0001-2205AB
  • ETI0001-2205A6
  • ETI0001-2205A8
  • ETI0001-2205E1
  • ETI0001-2205B4
  • ETI0001-2205EA

For more information on these variations, please contact us through the form below.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

 

ETI0001-2205, 3000 VA, UPS for the AN/TPS-77 Radar

NSN: 6120-01-535-9860
Rugged Tactical Power® UPS with Global Input, Maintenance Bypass and User Replaceable Battery Drawer

For use on: AN/TPS-77 Long Range Surveillance Radar

  • Tactical UPS® Rugged Rack Mount 3.0 kVA UPS
  • Plug Compatible Replacement for DRS UPSI 3000TR-III
  • Including Auto-ranging Global Isolated Input with PFC,
  • Manual Bypass and Front Access Swappable Battery Module
  • Additional Features Include Battle-short Override, Onboard Fuse Spares
  • Elapsed Time Maintenance Indicator Plus Reduced Rack Space

The field-proven Tactical Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size, and lightweight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed, or fixed locations with controlled or uncontrolled environments. The ETI0001-2205 is being used as a power source in global defense applications because of the stringent performance and reliability requirements. 

The heavy-duty UPS and Battery chases have rounded metal corners and rugged handles front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.  The internal intelligent thermal sensors provide monitoring of unit temperatures, with both local and remote Battle-short override capability of thermal shutdown for emergency scenarios. Battle-short can be engaged via a remote contact input or via a software command. When in Battle-short, an audible alarm is sounded and an indicator is lit. The high-intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.

The internal shielded input transformer provides galvanic isolation with provisions for nominal 100, 115, 120, 208, 220, 230, and 240 VAC input voltages, 50 or 60 Hz. Special EMI/RFI filters, input power factor correction, and inrush current limiting minimize both input current and harmonics.

The built-in Elapsed Time Indicator logs the hours of operation of the UPS as well as that of the equipment powered by the UPS. This can be used to plan preventative maintenance of the entire system. The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high-intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the onboard spare fuses, MTTR is reduced to less than 15 minutes.

Further, all front panel devices are recessed to prevent damage or accidental operation. The input circuit breaker and the galvanic isolation transformers all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. The Maintenance Bypass Switch can be used to remove the UPS electronics module from service while still providing power to the connected loads.

The rear panel provides locking connectors for the input and output power. Removable, washable air filters combined with high capacity stainless steel ball-bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the rear vents, with alternate airflow directions optional.

The ETI0001-2205 has the added benefit of having a field-replaceable battery via a front draw-out battery module. The external battery connector allows the safe and easy addition of the standard or extra battery modules without having to shut the unit down. The batteries are maintenance-free with immobilized electrolytes and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

Also available in this product series:

  • ETI0001-2205E2
  • ETI0001-2205A3
  • ETI0001-2205E1 The standard height version (6U total versus 5U) of this unit that is totally backward compatible.
  • ETI0001-2205AA
  • ETI0001-2205AB
  • ETI0001-2205A6
  • ETI0001-2205A8
  • ETI0001-2205E1
  • ETI0001-2205B4
  • ETI0001-2205EA

For more information on these variations, please contact us through the form below.

  • See the Power Distribution Units section for a listing of stand alone PDUs
  • See the N5 Series for a version of this UPS with an integrated PDU and remote control.

Overall, the Military Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

 

Additional information

Weight 132 lbs
Dimensions 23.5 × 19 × 8.75 in

Technical Specifications

AC OUTPUT
Output voltage: 120 VAC true sinewave standard,
100, 110, 115, 120, or 127 selectable output voltages
Output rating: UPS 3000 VA 0.7 pf standard
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 50 or 60 Hz user selectable
400 or 1000 Hz output available as an option
Operational status AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload, Warm temperature, Hot temperature, Fan fail and Battleshort LEDs,
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
Optional SNMP/HTTP, Asynchronous serial COM port
AC INPUT
Input voltage: Nominal 100, 120, 220, 240 VAC, 1-phase
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 95% typical
Input/output isolation: 3000 VA, up to 120 dB common mode, <5.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole 100 G shock rated circuit breaker (CB1)
plus UPS input fuses (F2)
Input power connections: MS 3102R-24-22P, 4 pin, locking
EXTERNAL BATTERY
External battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
External battery life: Rated for continuous service life of 5 years
External DC protection: Front panel mounted fuses (F1)
Internal battery time: Standard battery module: 5 minutes @ 2100 watts load
Internal battery recharge: Recharged to 95% in <5 hours
Internal battery replacement: Hot swap drawout/plug-in module from front of unit
<3 minutes to change battery modules
Battery expansion: Up to 24 hours w/ Battery Expansion Modules
DISTRIBUTION PANEL
Output circuits: Six AC outputs standard
Output control: Circuit breaker (CB1)
Battleshort to inhibit shutdown when engaged
Optional Remote ON/OFF of each load
Output receptacles: AC output NEMA 5-20R 3-pin standard
MECHANICAL
Dimensions (H x D x W):
2U UPS Module
3U Battery Module
3.50 (2U) x 23.5 x 19.0 in (89 x 597 x 483 mm)
5.25 (3U) x 23.5 x 19.0 in (133 x 597 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight:
2U UPS Module
3U Battery Module
37 lb. (17 kg) UPS with lift handles front and rear
95 lb. (43 kg) Battery with lift handles front and rear
Audible noise: Less than 59 dB @ 5.0 ft., ANSI “A” scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Front intake, exhaust to rear, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 49,212 ft (15,000 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810F, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; Optional MIL STD 461E