The field proven Airborne Power®  UPS line is ideally suited for military, industrial, medical and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The”ETI0001-1240″ is being used by the US Air Force ECMO Cart project because of their stringent performance and reliability requirements.

The heavy-duty chassis, occupying only  3U (5.25″ high) of rack space and 18.5″ depth, has rounded metal corners and rugged handles front and rear, aiding in safe handling. The companion 2U(3.5″ high) Battery Expansion Modules are designed to be daisy chained to bring the backup time to 4 hours in the typical configuration.  In the typical ECMO Cart application, the base UPS unit and up to four Battery Modules are mounted in the lower underside section of the patient cart. Both module chassis are constructed of brushed aluminum to minimize overall weight. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.

The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. This special transformer and filters result in ultra low input leakage current required for medical applications. The unit also operates as a frequency converter, taking 46-440 hertz input and converting it to clean, uninterruptible 60 hertz power. The input switch and the galvanic isolation transformer all provide a double pole isolated source for systems or locations where phase references and grounding are not consistent.  For scenarios that need hospital grade power immediately and no AC source is available to run the UPS, the Cold Start push button allows the unit to start and run from its battery modules before external AC is available.

The LED arrays keep the operator informed as to the unit’s status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Various optional power distribution controls are available which mount on the front panel or remotely.

The rear panel provides a locking connector for the input power and six hospital grade NEMA 5-15R output receptacles. Multiple input and output power panel options are available. Removable and washable air filters and a high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the front vent, with alternate air flow directions optional. The “ETI0001-1240” has the added benefit of having both an internal battery and external battery expansion modules. The external Battery Modules can be field replaced without having to shut the UPS down. This allows the backup time to be extended even further. The optional Battery Charger/Conditioner (which has aircraft and global input capability) is used to maintain the spare Battery Modules in ready condition at all times. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

For other versions of this product, inquire for information on these model numbers:

  • ETI0001-1240A1 (Model #: ETI0001-N3-1.0) w remote on/off
  • ETI0001-1240A2:  00 Watt UPS with Universal AC Input, aka ETI0001-1240AZ  (Model #: ETI0001-N3-1.0) w remote on/off, Schlumberger Part #: 100629876
  • ETI0001-1240AA (Model #: ETI0001-N3U-KI-1.0) w 461E surface, Shock & Vibration
  • ETI0001-1240AB (Model #: ETI0001-N3U-KI-1.0) w 461E surface, Shock & Vibration, without batteries
  • ETI0001-1240AC (Model #: ETI0001-N3U-KIF4-1.0) w 461E surface, Shock & Vibration with SNMP but no battery
  • ETI0001-1240AD (Model #: ETI0001-N3-1.0) w 461E surface, Shock & Vibration & remote on/off switch, Steel Chassis
  • ETI0001-1240AE (Model #: ETI0001-N3-1.0) w 461E surface, Shock & Vibration & remote on/off switch, Aluminum Chassis
  • ETI0001-1240AF (Model #: ETI0001-N3U-KI/2.0)
  • See the N5 Series ETI0001-1479 for a version of this UPS with an integrated PDU and remote control.
  • See the Power Distribution Units section for a listing of stand alone PDUs.

Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

ETI0001-1240 Series, 1000 VA and Frequency Converter for USAF

Rugged Mil Spec® Rack or Fixed Mount
1000 VA UPS
 and Frequency Converter
Used in Medical Applications

  • US Air Force ECMO Medical Patient Cart Application
  • 1.0 kVA Mil Spec UPS and Frequency Converter
  • Rugged Rack or Fixed Mount Unit
  • Reduced Depth
  • Multiple Battery Modules for up to 4 Hours of Battery Backup between Locations
  • Accepts both Aircraft Power and Commercial Power

The field proven Airborne Power®  UPS line is ideally suited for military, industrial, medical and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The"ETI0001-1240" is being used by the US Air Force ECMO Cart project because of their stringent performance and reliability requirements.

The heavy-duty chassis, occupying only  3U (5.25" high) of rack space and 18.5" depth, has rounded metal corners and rugged handles front and rear, aiding in safe handling. The companion 2U(3.5" high) Battery Expansion Modules are designed to be daisy chained to bring the backup time to 4 hours in the typical configuration.  In the typical ECMO Cart application, the base UPS unit and up to four Battery Modules are mounted in the lower underside section of the patient cart. Both module chassis are constructed of brushed aluminum to minimize overall weight. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration.

The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. This special transformer and filters result in ultra low input leakage current required for medical applications. The unit also operates as a frequency converter, taking 46-440 hertz input and converting it to clean, uninterruptible 60 hertz power. The input switch and the galvanic isolation transformer all provide a double pole isolated source for systems or locations where phase references and grounding are not consistent.  For scenarios that need hospital grade power immediately and no AC source is available to run the UPS, the Cold Start push button allows the unit to start and run from its battery modules before external AC is available.

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Various optional power distribution controls are available which mount on the front panel or remotely.

The rear panel provides a locking connector for the input power and six hospital grade NEMA 5-15R output receptacles. Multiple input and output power panel options are available. Removable and washable air filters and a high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the front vent, with alternate air flow directions optional. The "ETI0001-1240" has the added benefit of having both an internal battery and external battery expansion modules. The external Battery Modules can be field replaced without having to shut the UPS down. This allows the backup time to be extended even further. The optional Battery Charger/Conditioner (which has aircraft and global input capability) is used to maintain the spare Battery Modules in ready condition at all times. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

For other versions of this product, inquire for information on these model numbers:

  • ETI0001-1240A1 (Model #: ETI0001-N3-1.0) w remote on/off
  • ETI0001-1240A2:  00 Watt UPS with Universal AC Input, aka ETI0001-1240AZ  (Model #: ETI0001-N3-1.0) w remote on/off, Schlumberger Part #: 100629876
  • ETI0001-1240AA (Model #: ETI0001-N3U-KI-1.0) w 461E surface, Shock & Vibration
  • ETI0001-1240AB (Model #: ETI0001-N3U-KI-1.0) w 461E surface, Shock & Vibration, without batteries
  • ETI0001-1240AC (Model #: ETI0001-N3U-KIF4-1.0) w 461E surface, Shock & Vibration with SNMP but no battery
  • ETI0001-1240AD (Model #: ETI0001-N3-1.0) w 461E surface, Shock & Vibration & remote on/off switch, Steel Chassis
  • ETI0001-1240AE (Model #: ETI0001-N3-1.0) w 461E surface, Shock & Vibration & remote on/off switch, Aluminum Chassis
  • ETI0001-1240AF (Model #: ETI0001-N3U-KI/2.0)
  • See the N5 Series ETI0001-1479 for a version of this UPS with an integrated PDU and remote control.
  • See the Power Distribution Units section for a listing of stand alone PDUs.

Overall, the Rugged Power line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

Additional information

Weight 74 lbs
Dimensions 18.5 × 19 × 5.25 in

Technical Specifications

ETI0001-1240

AC OUTPUT
Output voltage: UPS 120 VAC true sinewave standard, up to 600 VAC optional
Output rating: UPS 1000 VA standard in 4U x 18.5″ deep
0.65-0.75 pf standard, optional configurations to 24,000 VA
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Nominal 115 VAC, optional autoranging input of 85-270 VAC
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 440 Hz standard
Input power factor: Better than 99% typically
Input/output isolation: 1000 VA, up to 120 dB common mode, <700 microampere leakage
Optional <50 microampere for commercial version w/o Mil Std 461
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole switch w/ fuse, optional circuit breaker
Cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking
INTERNAL BATTERY
Internal battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Internal battery life: Rated for continuous service life of 5 years
Internal DC protection: Front panel mounted fuse standard
Internal battery time: 8+ minutes @ 100% load, 20+ minutes @ 50% (base UPS only)
Internal battery recharge: Recharged to nominal in <8 hours
Internal battery replacement: Drawout/plug-in module from front of unit
EXTERNAL BATTERY
External battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
External battery life: Rated for continuous service life of 5 years
External DC protection: Rear panel mounted fuse standard
External battery time/module: 65+ minutes @ 100% load, 130+ minutes @ 50% per module
External battery recharge: Recharged to nominal in twenty times the discharge time
External battery replacement: Drawout/plug-in module from front of unit
DISTRIBUTION PANEL
Output circuits: Six outputs standard, optional configurations
Output control: Optional remote control panel w/rocker switches
Output receptacles: NEMA 5-15R Hospital Grade, 3 pin
MECHANICAL
Dimensions ( H x D x W ):
UPS
Each 2U Battery Module
5.25 (3U) x 18.5 x 19.0 in (133 x 470 x 483 mm)
3.50 (2U) x 18.5 x 19.0 in (89 x 470 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight:
UPS base unit only
Each 2U Battery Module
74 lb. (34 kg) UPS with lift handles front and rear
77 lb. (35 kg) Battery with lift handles front and rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI “A” scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Rear intake, exhaust to front, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461